Measurements For Temperature Sensor; Information On Refrigerant - Bosch Compress 7400i AW 5 OR Installer's Manual

Air to water heat pump
Table of Contents

Advertisement

Technical information
9.4.3

Measurements for temperature sensor

r..
°C
°C
– 40
154300
5
– 35
111700
10
– 30
81700
15
– 25
60400
20
– 20
45100
25
– 15
33950
30
– 10
25800
35
– 5
19770
40
± 0
15280
45
Table 7 Sensor TA4, TL2, TR4, TR5
°C
°C
– 20 96358
15
15699
– 15 72510
20
12488
– 10 55054
25
10001
– 5
42162
30
8060
± 0
32556
35
6536
5
25339
40
5331
10
19872
45
4372
Table 8 Sensor TC3, TR3
°C
°C
– 20 198500
15
31540
– 15 148600
20
25030
– 10 112400
25
20000
– 5
85790
30
16090
± 0
66050
35
13030
5
51220
40
10610
10
40040
45
8697
Table 9 Sensor TR1, TR6
9.5

Information on refrigerant

This device contains fluorinated greenhouse gases as refrigerant. The
device is hermetically sealed. You will find the information on the
refrigerant according to the Regulation (EU) No 517/2014 on
fluorinated greenhouse gases in the operating instructions of the device.
Information for the installer: If you refill refrigerant, enter the additional
charge size and the total charge size of the refrigerant in the table
"information on refrigerant" of the operating instructions.
22
r...
r...
°C
11900
50
1696
9330
55
1405
7370
60
1170
5870
65
980
4700
70
824
3790
75
696
3070
80
590
2510
85
503
2055
90
430
°C
°C
50
3605
85
1070
55
2989
90
915
60
2490
65
2084
70
1753
75
1480
80
1256
°C
°C
50
6899
85
2123
55
5937
90
1816
60
4943
95
1559
65
4137
100
1344
70
3478
105
1162
75
2938
110
1009
80
2492
1156
879
Compress 7400i AW – 6721840487 (2021/10)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Compress 7400i aw 7 or

Table of Contents