Explanation Of The Channel/Technology Parameters - Siemens SIMATIC ET 200SP Manual

Analog output module aq 4xi hart hf (6es7135-6td00-0ca1)
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

See also
Parameter assignment and structure of the channel/technology parameters (Page 53)
5.1.2

Explanation of the channel/technology parameters

Output type/range
The analog module has the following output ranges:
Table 5-2
Type of output
Disabled
Current
Current
Current
An overview of the output range, overflow and overrange etc. can be found in the appendix
"Analog value display (Page 66)".
Settling time dependent on the activation of HART communication
You can find the settling time without HART communication (x ms) in section "Technical
specifications of the AQ 4xI HART (Page 45)".
Figure 5-1
If HART communication is activated for the output range, the settling time of the output values
can vary (max: 50 ms).
Analog Output Module AQ 4xI HART HF
Manual, 05/2019, A5E35098013-AA
Output range
Output range
-
0 to 20 mA
4 to 20 mA
4 to 20 mA HART
Example diagram of settling time without HART communication
Parameters
5.1 Parameters of AQ 4xI HART
Resolution
-
16-bit including sign
16-bit including sign
16-bit including sign