Parameters
5.1 Parameters of AQ 4xI HART
Potential group
Specifies that a BaseUnit with supply voltage infeed is located in this slot (see system manual
ET 200SP Distributed I/O System
58649293)).
5.1.3

HART mapping parameters

A maximum of 4 HART variables can be configured (mapped) to the address space of the
module with the HART mapping parameters.
Each HART variable occupies 5 bytes of input data. As soon as you configure (map) at least
one HART variable in the input address space, the addresses for all four variables are allocated
(20 bytes).
With PROFIBUS DP GSD configuration with HART variables, the HART variables cannot be
directly configured. The four secondary variables are supplied in ascending channel order in
the address space of the module.
When required, this can be changed using data record 140; see section Parameter assignment
and structure of the HART mapping parameters (Page 55).
Parameters
Table 5-3
Parameter
Variable
0
Variable
1
32
Configurable HART mapping parameters
Value range
Chan‐
0...3
nel
Type
● Non / Cir
● Primary
● Secondary
● Tertiary
● Quaternary
Chan‐
0...3
nel
Type
● Non / Cir
● Primary
● Secondary
● Tertiary
● Quaternary
(http://support.automation.siemens.com/WW/view/en/
Default
0
Non / Cir
0
Non / Cir
Configuration in
With GSD file PRO‐
RUN
FIBUS DP
Yes
0
Yes
Secondary
Yes
1
Yes
Secondary
Analog Output Module AQ 4xI HART HF
Manual, 05/2019, A5E35098013-AA