Explanation Of The Parameters - Siemens SIMATIC ET 200SP Manual

Analog input module ai 8xi 2-/4-wire ba
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Parameters/address space

4.3 Explanation of the parameters

4.3
Explanation of the parameters
Diagnostics: No supply voltage L+
Enabling of the diagnostics for no or insufficient supply voltage L+.
Diagnostics: Short-circuit to ground
Enabling of the diagnostics if a short-circuit of the encoder supply to ground occurs.
Diagnostics: Overflow
Enabling of the diagnostics when the measured value exceeds the overrange.
Diagnostics: Underflow
Enabling of the diagnostics when the measured value falls below the underrange.
Diagnostics: Wire break
Enabling of the diagnostics if the module has no current flow or the current is too weak to be
measured at the relevant input.
The wire break and underflow diagnostics can be activated simultaneously. If both
diagnostics events occur simultaneously, the Diagnostics: Wire break is output.
Measurement type/measuring ranges
See the section Measurement types and measuring ranges (Page 13).
16
Analog input module AI 8xI 2-/4-wire BA (6ES7134-6GF00-0AA1)
Manual, 03/2015, A5E34941201-AA