Explanation of the parameters

Diagnostics no supply voltage L+
Enabling of the diagnostics for no or insufficient supply voltage L+.
Diagnostics short-circuit to ground
Enabling of the diagnostics in the event of a short-circuit of the encoder supply to ground or
of an input to the encoder supply.
Diagnostics overflow
Enabling of the diagnostics when the measured value exceeds the overrange.
Diagnostics underflow
Enabling of the diagnostics when the measured value falls below the underrange.
Diagnostics wire break
Enabling of the diagnostics if the module has no current flow or the current is too weak
to be measured at the relevant input.
The wire break and underflow diagnostics can be activated simultaneously. If both
diagnostics events occur simultaneously, the wire break diagnostics info is output.
Type/range of measurement
See the section Measuring types and measuring ranges (Page 12).
Analog Input Module AI 4xI 2-/4-wire ST (6ES7134-6GD00-0BA1)
Manual, 07/2014, A5E03551866-AC