EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Contents Symbols and illustrations ..............................4 Validity .....................................4 Product liability..................................4 Notes ....................................5 Important safety instructions ..................................5 Installation details ......................................5 Safe operation ........................................5 Inspection of installed system ..................................5 Disposal of the door system..................................6 Abbreviations................................6 Control unit and supply terminals ........................7 Control unit .........................................7...
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Symbols and illustrations Warning notices Warning notices are used in these instructions to warn you of property damage and personal injury. Always read and observe these warning notices. Follow all measures that are labelled with the warning symbol and warning word. Warning Warning word Meaning symbol...
à Unauthorised modifications to the system release GEZE from liability for any resulting damages. à GEZE makes no guarantee for combinations with third-party products. In addition, only original GEZE parts may be used for repair and maintenance work. à Connection to the mains voltage must be carried out by a qualified electrician. Perform the power connection and equipment earth conductor test in accordance with VDE 0100 Part 610.
Abbreviations EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Disposal of the door system à The door system is made up of materials that should be sent for recycling. The individual components have to be sorted in accordance with their material type. à...
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Control unit and supply terminals Control unit and supply terminals Control unit DCU201 Motor AC IN Encoder Encoder Motor TEMP TEMP DCU202 DCU204 DCU103 1 2 3 PROG CAN terminating resistance inactive DCU200 CAN terminating resistance active...
Control unit and supply terminals EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Supply terminals Max. permissible current drawn at 24V (terminals 1 / 2) with à EMD, EMD-Invers: max. 1.2 A à EMD-F: max. 1.0 A PE1 PE2 RSZ GND DCU201, DCU204, RSZ 24V...
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Safety sensor, open and close Safety sensor, open and close In the case of 2-leaf systems connect the safety sensors of the active leaf with the active leaf control unit and those of the fixed leaf with the fixed leaf control unit.
Page 10
Safety sensor, open and close EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers 4.1.1 Monitoring closing and opening Setting the parameter "Contact type": à DPS: ("normally open") (factory setting). à ST220: Set the "Input signals", "SI1 – terminal SIS", "SI1 contact state"...
Page 11
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Safety sensor, open and close 4.1.2 Monitoring opening Setting the parameter "Contact type": à DPS: ("normally open") (factory setting). à ST220: Set the "Input signals", "SI3 – terminal SIO", "SI3 contact type" to "normally open" (factory setting).
Safety sensor, open and close EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers 4.2.4 GC 334 connection over interface GC 334 The GC 334 interface is used to connect a customer's existing cable transition. GC 334 module GC 334 Module GC 334 module GC 334 Module 13 SIO...
Page 15
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Safety sensor, open and close 4.3.1 Monitoring closing and opening Setting the parameter "Contact type": à DPS: ("normally open") and ("normally open") (factory setting). à ST220: Set the "Input signals", "SI1 – terminal SIS", "SI1 contact state" to "normally open" and "SI3 –...
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Internal contact sensor Internal contact sensor à The KI input is active in the operating modes AU and LS. à In the case of 2-leaf systems the internal contact sensor (KI) can be connected to the active leaf control unit or to the fixed leaf control unit.
External contact sensor EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers External contact sensor à The input KA is only active in the AU operating mode. à In the case of 2-leaf systems, the external contact sensor can be connected to the active leaf control unit or to the fixed leaf control unit.
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Radio activation Radio activation à Follow installation instructions and user manual. Setting the parameter "Contact type": à DPS: (factory setting). à ST220: Set the "Signals", "Input signals", "KI", "KI contact state" or "KA", "KA contact state" to "normally closed".
Push And Go EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Push And Go WARNING Risk of injury due to crushing and shearing! During an activated Push And Go function door handles can form potential danger points. à The Push And Go function allows activation of the drive without contact sensors being used. à...
Page 21
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Configurable inputs à Parameter setting: à DPS: (operating mode "Off"), (2-leaf opening) or (1-leaf opening). à ST220: Set "PE1 function" or "PE2 function" to "Off NO", "2-leaves Open NO" or "1-leaf open NO". oder 2 24V 51 PE1...
Page 22
Configurable inputs EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Parameter setting (For 2-leaf drives, the settings on the active leaf control unit determine the hold-open time) DPS: à to for: 1st switch contact = open door / 2nd switch contact = close door. If no second switch contact takes place, the door remains open until the operating mode is changed.
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Configurable outputs Configurable outputs Various switching functions are assigned to the configurable outputs PA1 and PA2 (see chapter 24, “Service menu”). To operate the display programme switch DPS see chapter 24.3, “Display programme switch (DPS)”. To operate the service terminal ST220 see chapter 24.2, “Service menu ST220”.
Page 24
Configurable outputs EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Warningsignal à The function is used to signal door movement (cyclical switching on/off of a customer signal transmitter while the door is opened or closed). Maximum permissible total current draw by the control unit. à...
Page 25
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Configurable outputs Motor fan à The function is used to cool the drive in case of an excessive load. Axial fan, mat. no. 126895 à Parameter setting: PA1 PA2 PA1 PA2 à...
Configurable outputs EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Maintenance due à The function is used to signal that maintenance is due at the door drive to a customer building control centre. Connection to building control centre: See chapter 12.1 "Configurable output PA1", "Fault" à...
Page 27
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Configurable outputs Electric strike à The electric strike function is not permissible if the drive is used for the fire-protection area (EMD-F, EMD- Invers). à Only inductive DC electric strikes (without integrated electronics) may be connected to PA2. Electric strikes with integrated electronics, such as the types effeff 331, 331 U, 331 V, 332, 351 U, etc.
Configurable outputs EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Day-night changeover à For example, the function is used to switch a motor lock from day to night operation. The output switches to GND, if the operating mode LS, AU 1-leaf, DO, or AU 2-leaf is set. Connect a 24 V DC relay, mat.
à Activation of the electric strike is limited to 5 s plus the parametrised activation delay time For EMD Invers only use escape door opener, hold-open magnet or motor lock GEZE IQ Lock EL. à Hold-open magnet MA 500 with counter plate, mat. no. 024740, for the magnetic locking of emergency exit doors.
Page 30
Electric strike EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers 24V DC electric strike supplied on drive side à In the case of electric strikes with integrated electronics (capacitive load, e.g. type effeff 331, 331U, 331V, 332, 351U, 141, 142, 143, 143M, etc.) a resistor (10 Ohm, 5%, 1 W, metal layer, axial) has to be connected between 1 (GND) and 31 (TOEA) in order to limit the starting current.
à Motor lock with panic function GEZE IQ Lock EL for 1-leaf doors. The GEZE IQ Lock EL is a self-locking anti-panic motor lock with external control unit. To connect IQ Lock EL to EMD, EMD-F, EMD Invers, see motor lock IQ Lock EL wiring diagram.
Toilet control EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Toilet control Only operates with electric strike closed current. For connection and configuration of the electric strike, see chap- ter 13, “Electric strike”. oder PE1, PE2 PE1, PE2 oder oder PA1 PA2...
Operating mode EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers 15.2 Setting the mode of operation with switches The selected operating mode remains in place as long as a control signal is present at one of the programme switch inputs.
Operating mode EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers à The keypad programme switch and display programme switch can be connected to the control unit at the same time. à Operation at the TPS or DPS is not possible during the self-test, e.g. after changing the operating mode. The control unit can be configured using the display programme switch.
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers 2-leaf drives 2-leaf drives 16.1 Two automated door leaves Do not connect terminal 2. RS485 GF RS485 SF à For parameter settings, see chapter 23, “Commissioning and service”. 2 24V RS485-A 42 RS485-A RS485-B...
RWA emergency power control unit on EMD-Invers EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers RWA emergency power control unit on EMD-Invers à The RWA emergency power control unit is connected to the DCU204 PCB. à In the event of a fire alarm or power failure the electric strike and motor are disconnected from the control unit.
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers EMD-F, EMD-FIS, EMD-F/R on fire protection doors EMD-F, EMD-FIS, EMD-F/R on fire protection doors Pay attention to the wiring diagram and installation instructions of the smoke switch control unit. If the drive is used on fire protection doors, neither connection to a central reset switch provided by the customer nor the operation with a bypassed reset pushbutton is permissible.
Mains connection EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Mains connection Transom installation Transformer DCU2, mat. no. 105182 230V 50Hz GN/YE GN/YE GN/YE Mains fuse, provided by customer *) control unit AC IN Main switch (optional, provided by the customer) to second drive Transformer Cover earthing...
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Motor Motor WARNING Risk of injury due to link arm or lever arm snapping back (EMD F, EMD Invers)! Separate the motor from the control unit only when spring is relaxed. Connecting the latching action switch to DCU201 The latching action is triggered by a cam switch in the gearing during closing with spring force.
Door closer operation EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Rotary transducer on the gear: Set parameter "rotary transducer position" to (factory setting). D® Rotary transducer on the motor shaft: Set parameter "rotary transducer position" to D® Door closer operation If frail people and/or children use the door and the risk analysis states that appropriate safety measures must be selected, the "Door closer mode“...
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Basic functions Basic functions 22.1 Automatic mode à For automatic mode, the door leaf's hinge and opposite hinge side must be secured with safety devices (safety sensor strips) in accordance with DIN 18650 and EN 16005. The drive opens and closes the door automatically after activation with the speeds, hold-open times and func- tions set during commissioning.
Page 46
Basic functions EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Setting additional parameters: ST220 Opening and closing torque Opening force Closing force Door closing torque Opening time to limit the kinetic energy to 1.6 J when opening Acceleration opening Opening speed Acceleration closing Closing time to limit the kinetic energy to 1.6 J when closing...
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Basic functions Set the closing time with the parameter ("Speeds", "Close") so that they are greater than or equal to the value in the table. Use parameter ("Speeds", “Close manual") to set the closing time after a manual opening so that it is greater than or equal to the value in the table.
Page 48
Basic functions EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Servo function with fire alarm à Building approval is required for each individual case when using the function on fire protection doors. à The drive must be supplied by a safety power supply provided by the customer, or an uninterruptible power supply (UPS).
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Commissioning and service à The DO operating mode is disabled in the event of a fire alarm. SIS and SIO are not evaluated in the event of a fire alarm. The door closes upon expiration of the set servo duration ( à...
Page 50
Commissioning and service EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers WARNING Prohibited operation! Risk of injury! If the rotary transducer is mounted to the gear and parameter ("Encoder position") is set to (motor shaft) D® instead of to (gear), the door leaf will rotate at an excessively high speed.
Page 51
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Commissioning and service 23.2.2 Commissioning of a brand-new 2-leaf drive The active and fixed leaf control unit need to be configured separately. To configure the control units, disconnect the RS485 connection between the active and fixed leaf control unit (disconnect the RS485 plug from the DCU200).
Page 52
Commissioning and service EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Clear error memory Complete configuration of the active leaf control unit. Change to the service mode. Clear error memory Check the default setting of all the other parameters of the active leaf control unit and adapt if necessary. For 2-leaf drives: , if no mechanical closing sequence control à...
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Commissioning and service 23.2.6 Re-execute learning function for drive The drive must be “re-taught" after each change made to the drive, especially after changing the spring preload, the opening width, the fitting dimensions or changing the control resistor elements or changing the sensing field of the “Open”...
Page 54
Commissioning and service EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Disconnect the service terminal from the active leaf control unit and connect to the fixed leaf control unit. à In the menu "Door parameters", "Number of leaves": à...
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Service menu Service menu 24.1 Service terminal ST220 à Service terminal ST200, mat. no. 087261 à The drive can be commissioned with service terminal ST220, software version from v2.1. 24.1.1 Operation of ST220 Function Cursor upwards Increase number value...
Service menu EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers 24.2 Service menu ST220 24.2.1 Operating mode Designation Setting values Description Operating mode Operating mode Operating mode setting Night Shop closing Automatic Open Type opening 2. leaves open Open active and fixed leaves at activation 1.
Page 57
Open delay: Period which the motor lock has to unlock before the drive opens the door. GEZE bus address 0 … 99 Address for GEZE building system 24.2.3 Motion parameters Designation Setting values Description 05 … 40 … 90 Speeds Open Change value using ...
Page 58
Service menu EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Designation Setting values Description Hold-open times 2-leaf (Summer) 0 ... 1 ... 60 With activation KI, KA 2-leaf Opening (Au-So) Setting on GF control unit 0 ... 1 ... 60 1-leaf (Winter) With activation KI, KA 1-leaf Drive (Au-Wi, Au-So)
Page 59
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Service menu Designation Setting values Description Door closer mode Manual (ts = 00) Refer also to chapter 21, “Door closer operation”. Automatic (ts = 01) (ts = 02) Spring (only for EMD-F) Intervene manually not active Force for manually opening the...
Page 60
Service menu EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Designation Setting values Description current state State, contact type Display NA contact state unused Input NA without function Normally closed Normally open current state State, contact type Display LS contact state unused Input LS without function...
Page 61
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Service menu Designation Setting values Description current state State, contact type, function Display unused PE2 function Input PE2 without function Analogue programme switch Activate motor 2-leaves Open Open active and fixed leaves 1-leaf Open Only active leaf opens Sabotage...
Page 62
Service menu EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Output signals Designation Setting values Description current state State, contact type, function Display PA1 function unused Output PA1 without function Gong At activation KA in the operating mode AU and DO Error NC Fault message e.g.
Page 63
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Service menu Designation Setting values Description current state State, contact type, function Display unused PA2 function Output PA2 without function Gong At activation KA in the operating mode AU and DO Error NC Fault message e.g.
Page 64
Service menu EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers 24.2.5 Diagnostics Designation Setting values Description Current values Inputs SI1, SI3 0 V / 24 V 0 V / 24 V STOP Voltage at the terminal in V KB, KI, KA 0 V / 24 V NA, LS 0 V / 24 V 0 V / 24 V...
Page 65
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Service menu Designation Setting values Description Configuration Drive Ser No Serial number of the drive max. opening range Control unit Typ EMD DCU2, DCU2-F, DCU2-I Fet Dat Manufacturing date CW/Year Production test Start production test (only factory internal)
Page 66
à If the password has been forgotten, a special flash file with which the password on the control unit can be reset to 00 has to be requested from GEZE. à The password cannot be deleted by installing a new software version.
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Service menu 24.3 Display programme switch (DPS) The DPS can be used for commissioning and service. No. 151524 or 155809: à for changing the drive parameters à for "teaching" the drive à...
Page 68
Service menu EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Display Description Setting values Note Delayed closing 01 ... 15 16 Active leaf 0 s: Simultaneous closing of both leaves (only set for doors without rebate) 01–15 s: The active leaf closes at the latest when the fixed leaf has reached the closed position.
Page 69
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Service menu Display Description Setting values Note Configurable input 1 Unused Pushbutton OHZ: Unused Switch function with closing after hold-open time Operating mode Off For 2-leaf door, 1-leaf mode and Open 2-leaf à...
Page 70
Service menu EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Display Description Setting values Note Configurable output 2 Unused 01: At activation KA in the operating Gong mode AU and DO Error normally closed 02, 03: General fault message Error normally open 05: Activation of signal transmitter Fault display for MPS...
Page 71
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Service menu 4. Menu Display Description Setting values Note Operator type Only display, no setting option EMD-F EMD-Invers D® Rotary transducer position Motor shaft Rotary transducer on the motor shaft Gear Rotary transducer on the gear 1-leaf Drive...
"open" is taught during commissioning and can be corrected here. Maximum opening range of the door = 100 GEZE bus address 01…99 CAN address GEZE building system only effective for active leaf low energy mode (see chapter 22, “Basic functions”)
Page 73
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Fault messages Message on the Message on the ST220 Fault description (Active leaf ) electric strike does not block Locking mechanism (Active leaf ) electric strike does not trigger Unlocking SIS SF fault Testing (fixed leaf ) safety sensor "close"...
Fault messages EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Message on the Message on the ST220 Fault description Change in mode of operation: not possible (internal PS not set to 0, or MPS is parametrised). Operating mode Off ®s RESET On starting the learning procedure: Reset pushbutton not pressed or 24 V RSZ...
EMD / EMD-F / EMD-F-IS / EMD-F/R / EMD Invers Angle for setting low energy mode Angle for setting low energy mode See chapter 22.2.3 “Setting the minimum opening time and minimum closing time”.