Nominal Size Selection Calculation Formula; Installation; Example Of Piping - Yoshitake GP-1200 Installation And Operation Manual

Pressure reducing valve
Table of Contents

Advertisement

5.5 Nominal size selection calculation formula

The appropriate nominal size can be calculated by obtaining the Cv value for the operating conditions
in question, as shown below.
• Cv value calculation formula
P
>
1
P
2
2
Cv
P
<
1
P
2
2
Cv =
• Rated Cv value table (When Cv correction coefficient is C=1)
Nominal size
Rated Cv value
※  C orrection of rated Cv value
If the inlet pressure exceeds 0.7 MPa, and the pressure reducing ratio exceeds 10:1,
find the appropriate correction coefficient C using chart below, and multiply the rated
Cv value, and obtain the corrected Cv value.
1.0
0.9
(B)
0.8
0.7
0
0.02
0.04
P :Reduced pressure  MPa
2

6. Installation

6.1 Example of piping

Pressure
gauge
Wk
=
+
138
P(P
P
)
1
2
Wk
120P
1
15A
20A
25A
1
2.3
4
(A)
0.06
0.08
0.10
Drain separator
DS-1
Strainer
Stop
valve
Stop
valve
Stop
Sight glass
valve
1810
Blow
Trap
W: Max. steam flow rate [kg/h]
P
: Inlet pressure [MPa・A]
1
P
: Reduced pressure [MPa・A]
2
ΔP: P
−P
1
k: 1+0.0013 × {super-heated steam
32A
40A
50A
6.5
9
16
[Ex.]
Take a pressure reducing valve whose inlet
pressure is 0.8 MPa, reduced pressure is 0.05
MPa. Find the inlet and reduced pressure
intersection point (A) at the left chart, then
draw a horizontal line in the leftward
direction to point (B) which indicates a
correction coefficient of 0.85. For a nominal
size of 25A, the corrected Cv value would be
calculated as follows:
4(rated Cv value) × 0.85(correction
coefficient) = 3.4
3 port
solenoid valve
By-pass
stop valve
Reducer
Stop
GP-1200
valve
Pressure reducing valve
‑6‑
[MPa]
2
temp.[℃]−saturated steam
temp.[℃]}
65A
80A
100A
25
36
64
Air pressure
Non-return
valve
Standard unit
Relief
pipe
Pressure
gauge
Safety
valve
■EPDT-101■