Product Overview

2
Product Overview
2.1

Introduction

The functionalities of the Beckhoff PCI card FC310x (as Master [} 10] and Slave [} 11]) for use under
TwinCAT (NCI, PTP, PLC and IO) is described below.
TwinCAT 2.7 does not support all the functions described below. TwinCAT 2.8 on the other hand supports all
functions described below, with the exception of redundancy and of the ADS server interface of the FC310x
as a slave (these will both be supported as from TwinCAT 2.9).
The following chapters also apply to the PROFIBUS connection for the CX1000 (CX1500-M310 (master) or
CX1500-B310 (slave)); the name FC310x then also refers to the CX1500-M310 master or CX1500-B310
slave connection.
2.2

FC310x - Technical Data

Technical Data
Bus system
Number of fieldbus channels
Data transfer rate
Diagnostics
Interface to the PC
Bus interface
Communication
Bus devices
Process image
Cycle time
Standard driver
Real-time driver
Supply voltage (PCI bus)
Current consumption (PCI bus, 5 V)
Power consumption from PCI bus
Weight
Dimensions (W x H x D, without slot panel)
Permissible ambient temperature range
during operation
Permissible ambient temperature range
during storage
Permissible relative air humidity
Vibration / shock resistance
EMC immunity / emission
Installation position
Approval
8
FC3101
PROFIBUS DP (standard), PROFIBUS DP-V1 (Cl. 1+2:
acyclic services, alarms), DP-V2, PROFIBUS MC (equidistant)
1
9.6 kbit/s – 12 Mbit/s
2 LEDs per channel
Plug-and-play PCI interface, 32 bit with 4 kbytes DPRAM per
channel
1 x D-Sub socket, 9-pin,
galvanically isolated
Master and slave functionality (also mixed)
per channel: max. 125 slaves with up to 244 bytes input,
output, parameter, configuration or diagnostic data per slave
Sum max.: 3 kbytes input and output data
differing DP cycle times per slave are possible using the CDL
concept
standard operating system driver for Intel-compatible NIC
TwinCAT driver for real-time Ethernet
5 V
typ. 600 mA
< 5 W
approx. 45 g
approx. 14 mm x 106 mm x 175 mm
0°C ... + 55°C
-25°C ... + 85°C
95 %, no condensation
conforms to EN 60068-2-6 / EN 60068-2-27
conforms to EN 61000-6-2 / EN 61000-6-4
variable
CE
Version: 3.0
FC3102
2
2 x D-Sub socket, 9-pin,
galvanically isolated
typ. 1000 mA
approx. 75 g
FC3101 and FC3102

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fc3101