Fig. 28 Twincat 2.9 - Fault Settings Dialog - Beckhoff FC3102 Documentation

For profibus
Table of Contents

Advertisement

FC310x as master
3.8.2.3
Fault Settings dialog
Fig. 28: TwinCAT 2.9 - Fault Settings dialog
SetPrm-Unlock before DP-Start-Up: Normally, during DP start-up, the DP master removes the cyclic
connections, so that the DP slave can always recognize that the DP master has restarted. In redundancy
mode, however, it may be specifically desirable for the DP slave to remain unaware of this, because the
switch-over from the primary master to the redundant master should not have any interactions for the DP
slave (see the Master Redundancy [} 38] chapter).
SetPrm-Unlock at DP-Shutdown: Normally, during DP shut-down, the DP master removes the cyclic
connections, so that the DP slave can always recognize that the DP master has stopped. In redundancy
mode, however, it may be specifically desirable for the DP slave to remain unaware of this, because the
switch-over from the primary master to the redundant master should not have any interactions for the DP
slave (see the Master Redundancy [} 38] chapter).
Operate-Delay: The DP master changes automatically, observing the Auto-Clear-Mode, into the operate
state when the task is started. The transition from Clear to Operate can be delayed with the Operate delay
time. In the Clear state, all the outputs are set to 0 (if the DP slave does not support Fail_Safe values) or to
the Fail_Safe value (if the DP slave supports Fail_Safe), whereas in the Operate state the outputs have the
values specified by the task.
Reaction on task STOP: It is possible to specify here whether the DP master should set the outputs to 0
when reaching a PLC stop or breakpoint, or should leave them unchanged (see the Fault Reactions [} 16]
chapter).
Task-Watchdog: The DP master changes automatically into the clear mode (the outputs of the slaves are
set either to 0 or to the fail-safe values) when it ceases to receive an interrupt from the associated task (e.g.
a PLC breakpoint has been reached, or the system has crashed). It is possible to specify here how many
missing tasks cycles can be tolerated before the master switches into the clear mode. This setting is
independent of the setting in the Clear mode.
FC3101 and FC3102
Version: 3.0
51

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fc3101

Table of Contents