Cooling - Samsung DVM PLUS III Technical Data Book

Hide thumbs Also See for DVM PLUS III:
Table of Contents

Advertisement

1. products(01~41)
3/14/08 22:01
N N
N N
o o
o o
As shown in the example, when the combination rate exceeds 100%, the capacity of outdoor unit is
calculated using 100, 110, 120, 130% tables. However, when the combination rate is below 100%, use
capacity presented at the 100% table.
Thus, outdoor unit capacity can be calculated as follows:
Combination rate of actual indoor and outdoor units= 130%
120% < Combination rate of actual indoor and outdoor units < 130%
Combination rate of actual indoor and outdoor units= 120%
110% < Combination rate of actual indoor and outdoor units < 120%
Combination rate of actual indoor and outdoor units= 110%
100% < Combination rate of actual indoor and outdoor units < 110%
Combination rate of actual indoor and outdoor units < 100%
Using capacity graph of max. piping length and level difference, get the capacity reduction ratio.
- Max. Piping length (outdoor unit to the farthest indoor unit): 60m
- Level difference: -20m
From the above conditions, as the capacity of outdoor unit is 92.2%, its actual capacity is 51.5kW x 92.2% = 47.5kW
(51.5kW: RVXVHT180** 105% combination capacity)
◆ Compact combinations
18HP (Heat Pump / Heat Recovery)

Cooling

Page 37
t t
t t
e e
e e
94%
50
95%
40
30
20
100 %
10
0
0 10
20
30
40
50
-10
-20
-30
-40
Refer to 130% capacity table
Calculate with 120% & 130%
capacity table
Refer to 120% capacity table
Calculate with 110% & 120%
capacity table
Refer to 110% capacity table
Calculate with 100% & 110%
capacity table
Refer to 100% capacity table
92.2%
89.9%
100 % 95%
60
70
80
90
100 90
100 110 120 130 140 150 160 170 180 190 200
Pipe length(m)
90%
Main pipe
size-up
84.9%
I-37