1. products(01~41)
3/14/08 22:01
New technology of
2
2
2-1. Digital hybrid system
DHS (Digital Hybrid System) is a brand new concept system composed of DVI (Digital Vapor Injection)
compressor, vapor injection technology and turbo intercooler. These 3 factors together provide highly efficient
performance.
1) DVI compressor
Efficient and reliable DVI (Digital Vapor Injection) compressor
coupled with vapor injection technology has been applied to
improve cooling and heating performance and energy
efficiency.
2) Vapor injection technology
Improved cooling and heating performance and COP by a new technology of two stage compression.
As injecting optimized mid-range pressure refrigerant, this technology achieved the high heating
performance and COP under the lowest temperature, which leads the industry.
• Increase refrigerant flow rates with a new vapor injection technology.
• Improved sub-cooling necessary for long piping installation while increasing cooling and heating performance and COP.
Evaporator (ID)
DVI compressor
Vapor injection
Condenser (OD)
3) Turbo intercooler
Turbo intercooler (Shell & tube type) improves cooling and heating COP and secures reliable operation of
installation with long piping (200m).
❷
Subcooling liquid refrigerant
❹
Low temperature gas
refrigerant
❸
❶
Page 11
2nd
Mo
EEV
Solenoid Valve
Mi
Flash tank
1st
EEV
Mo + Mi
Low temp. liquid
refrigerant
Saturated liquid
refrigerant
DVM PLUS III, DVM PLUS III HR
DVI
Vapor
Compressor
Injection
PWM valve
Discharge port
Vapor
injection
Suction port
port
Oil port
More mass flow passing Indoor
unit increases heating capacity.
Mo + Mi
1st Expansion
2nd
Mi
Expansion
Vapor injection
Mo
Vapor injection reduces the liquid enthalpy in flash
tank, facilitating heat exchanger to absorb heat more.
Temperature
❹
❶
High
❷
❸
❸
Low
❶
Turbo
Intercooler
Gas inlet
Injection
point
Enthalpy (kJ/kg)
❷
❹
I-11