3) Select preliminary outdoor units
Before selecting outdoor units, decide the permissible combination rates for indoor and outdoor unit.
➊
Determining permissible combination rates for indoor and outdoor units: Below 110%
❷
Calculate the sum of total capacity of the selected indoor units: 52.9kW (Refer to the table below)
52.9kW = [3.6kW + 7.1kW + 5.6kW + 7.1kW + 11.2kW + 7.1kW + 11.2kW]
Zone
Total cooling load (kW)
Sensible heat load of
cooling (kW)
Indoor unit type
Determined model
Indoor unit capacity (kW)
❸
Select outdoor units
As the sum of all
indoor unit capacity
Outdoor unit capacity
❈ Therefore, as 52.9kW/1.1 should meet outdoor unit capacity and less ( 52.9 kW/1.1
capacity of outdoor unit should be larger than 48.1kW.
Hence, select the outdoor unit RVXVHT180GE(refer to the table below).
OUTDOOR TYPE
Model
Power Supply
Mode
Horse Power
Performance
❹
Calculating actual combination rates of indoor and outdoor units
As outdoor unit RVXVHT180✴✴'s cooling capacity is 50.4kW,
Actual combination rate is
Page 35
A
B
3.3
6.3
2.2
5.0
Vivace
Slim duct Mini 4way
AVXWVH036 AVXDSH071 AVXCMH056 AVXC4H071 AVXDSH112 AVXTFH071 AVXC4H112
3.6
7.1
Permissible
≤
combination rate,
RVXVH(R)T160GE
ø, V, Hz
-
HP
kW
✻ 1)
Cooling
✻4
Btu/h
Capacity
kW
Heating
✻ 2)
Btu/h
Capacity Control Step
-
All indoor unit capacity (52.9kW)
Outdoor unit capacity (50.4kW)
C
D
4.5
7.1
3.0
4.9
4way
Slim duct
5.6
7.1
As the sum of all
indoor unit capacity
permissible combination rate
≤
RVXVH(R)T180GE
3, 380~415, 50
3, 380~415, 50
HP/HR
HP/HR
16
18
44.8
50.4
152,900
171,900
50.4
56.7
172,000
193,500
=
E
F
G
10.4
7.0
10.0
8.0
5.1
7.0
Ceiling
4way
11.2
7.1
11.2
Outdoor unit
≤
capacity.
outdoor unit capacity), cooling
RVXVH(R)T200GE
RVXVH(R)T220GE
3, 380~415, 50
3, 380~415, 50
HP/HR
HP/HR
20
22
56.0
61.6
191,000
210,100
63.0
69.3
215,000
236,500
approx. 105%.