External contact control system
5
5-1. Key-tag interface module (MIM-B02)
4) Additional functions
Option switch setting
DIP SW
K1
K2
K3
K4
❈ When K3 =ON, K4 doesn't work
❈ Remote controller :Wired/Wireless remote controller
V-158
3/6/08 14:09
Page 158
These can set indoor unit operation patterns when the external contact is input.
State
Note
When the I/M contact is Close, indoor unit turns OFF
ON
(When the contact is Close, remote controller can't be used).
K3=ON
When the I/M contact is Open, indoor unit remains in the OFF state
OFF
(When the contact is Open, remote controller can be used).
When the I/M contact is Close, indoor unit turns ON
When the I/M contact is Close, indoor unit turns OFF.
ON
(Remote controller can be used.)
K3=OFF
When the I/M contact is Close, indoor unit turns OFF
When the I/M contact is Open, indoor unit turns ON.
OFF
(Remote controller can be used.)
When outdoor unit uses key-tag I/M only
ON
(DVM, DVM PLUS, DVM PLUS II, FJM, mini DVM).
When outdoor unit uses key-tag I/M and centralized controller together
OFF
(Only for DVM HR/PLUS II HR).
ON
The external contact turns indoor unit OFF only.
OFF
The external contact turns indoor unit ON and OFF.
After power reset, ignore initial I/M contact state.
ON
And start to control indoor unit by next contact state.
After power reset,start to control indoor unit by initial I/M contact state.
- Available for Indoor unit which doesn't support Auto restart.
OFF
- When indoor unit turns ON by initial contact state, Indoor unit runs Auto mode.
Setting temperature 24, Auto fan speed.