Samsung DVM PLUS III Technical Data Book page 209

Hide thumbs Also See for DVM PLUS III:
Table of Contents

Advertisement

3-1.DVM,HR3_Outdoor(002~037)
Type
Model
Compact
Basic
Power Supply
Mode*
1)
Performance
Horse Power
Capacity
Cooling*
Heating*
Power
Nominal input
Cooling
Heating
Cooling
Nominal running
current
Heating
Circuit Breaker (MCCB/ELB)
Cooling
COP
Heating
Compressor
Model
Type
Number
Piston Displacement
Output
Lubricant
Type
Charging
Type/Control
Fan
Motor Output
Airflow Rate
External Static
Max.
Pressure
Safety
Mechanical Type
Devices
Electronic Type
Piping
Liquid
Connections
Gas
Discharge Gas
Oil (Flare)
Installation Limitation
Max. Length
Max. Height
Refrigerant
Type
Factory Charging
Sound*
4)
Sound Pressure
Sound Power
Set Size
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Main Power (Below 50m)
Cable
Communication
Operating
Cooling
Heating
Temp. Range
Standard Accessories
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent piping length : 7.5m, Level differences : 0m
*3) Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
3/21/08 11:19
Page 27
42 HP
RVXVRT080GE
RVXVRT100GE
RVXVRT120GE
1
RVXVRT140GE
1
RVXVRT160GE
1
ø/V/Hz
3/ 380~415/ 50
-
HR
HP
42
2)
kW
117.6
Btu/h
401,300
3)
kW
132.3
Btu/h
451,500
kW
36.20
kW
34.80
A
66.9
A
67.1
A
125
-
3.25
-
3.80
-
ZPJ61✴ ZPJ72✴
ZPJ83✴
-
Digital scroll
EA
2
1
cc/Rev
67.1
77.2
kW
5.81
8.02
-
3MAF POE
cc
1,685
1,685
-
Propeller/BLDC
W
m
3
/min
180 x 1 + 210 x 2
mmAq
8
Pa
78.5
-
High pressure switch
-
Crank Case Heater
-
Fuse for PCB
-
Over voltage protection
-
Current Transformer
-
Fan over heat/current protector
ø, mm
19.05
ø, mm
38.10
ø, mm
31.75
ø, mm
6.35
m
200
m
50 (40)
-
R410A
kg
7.5 x 1 + 11 x 2
dB(A)
64
dB(A)
kg
242 x 1 + 323 x 2
kg
255 x 1 + 340 x 2
mm
(880 x 1,703 x 765) x 1+ (1,200 x 1,703 x 765) x 2
mm
(948 x 1,868 x 832) x 1+ (1,268 x 1,868 x 832) x 2
mm
2
25
mm
2
0.75~1.50
°C
-5~43
°C
-20~24
-
-
44 HP
2
1
3/ 380~415/ 50
HR
44
123.2
420,500
138.6
473,000
36.80
35.80
65.9
69.9
125
3.35
3.87
ZPI 6 1✴
ZPI 7 2✴
ZPI 8 3✴
ZPJ61✴ ZPJ72✴
ZPJ83✴ ZPI 6 1✴
Fixed scroll
Digital scroll
2
2
1
3
58.1
67.1
77.2
67.1
58.1
4.93
5.81
8.02
5.81
4.93
3MAF POE
1,685
1,685
1,685
1,685
1,685
Propeller/BLDC
210 x 3
8
78.5
High pressure switch
Crank Case Heater
Fuse for PCB
Over voltage protection
Current Transformer
Fan over heat/current protector
19.05
38.10
31.75
6.35
200
50 (40)
R410A
11 x 3
65
323 x 3
340 x 3
(1,200 x 1,703 x 765) x 3
(1,268 x 1,868 x 832) x 3
25
0.75~1.50
-5~43
-20~24
46 HP
1
2
3/ 380~415/ 50
HR
46
128.8
439,600
144.9
494,500
40.60
40.40
71.8
73.8
125
3.17
3.59
ZPI 7 2✴
ZPI 8 3✴
ZPJ61✴ ZPJ72✴
ZPJ83✴ ZPI 6 1✴
Fixed scroll
Digital scroll
4
2
3
2
67.1
67.1
58.1
5.81
5.81
4.93
3MAF POE
1,685
1,685
1,685
Propeller/BLDC
210 x 3
8
78.5
High pressure switch
Crank Case Heater
Fuse for PCB
Over voltage protection
Current Transformer
Fan over heat/current protector
19.05
38.10
31.75
6.35
200
50 (40)
R410A
11 x 3
65
323x 3
340 x 3
(1,200 x 1,703 x 765) x 3
(1,268 x 1,868 x 832) x 3
25
0.75~1.50
-5~43
-20~24
ZPI 7 2✴
ZPI 8 3✴
Fixed scroll
4
67.1
5.81
1,685
III-27

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dvm plus iii hrMini dvm

Table of Contents