Connection Examples - Samsung DVM PLUS III Technical Data Book

Hide thumbs Also See for DVM PLUS III:
Table of Contents

Advertisement

05-1_control systems(002~045)
Control Systems
1
Individual control system
1
1-3. Wired remote controller

Connection examples

Individual control
Outdoor unit
Control
Display
Group control (1)
Outdoor unit
Control
MWR-TH01/MWR-SH00
Display
MWR-WS00
Group control (2)
Outdoor unit
Control
MWR-TH01/MWR-SH00
Display
MWR-WS00
V-28
3/15/08 4:09
Page 28
• MWR-TH01
Wired
• MWR-WS00
R/C
• MWR-SH00
Control 1 indoor unit with 1 wired remote controller
F1/F2
F3/F4
Wired R/C
Connected indoor unit
Operation status of the connected indoor unit
Control multiple indoor units with 1 wired remote controller
F1/F2
F3/F4
Wired R/C
All connected indoor units
Operation status of one of the connected indoor units on a random basis.
Operation status of one of the connected indoor units which has the earliest Main address.
Control multiple indoor units connected to different outdoor units
with 1 wired remote controller
F1/F2
F3/F4
Wired R/C
❈ Max. 16 indoor units can be connected.
All connected indoor units
Operation status of one of the connected indoor units on a random basis.
Operation status of one of the connected indoor units by the following standard.
- In case that all the Main addresses are different : displays the indoor unit which has the earliest Main address.
- In case that there exist the overlapped Main addresses and they are the earliest :
displays one of them on a random basis.
- In case that there exist the overlapped Main address and they are not the earliest :
displays the indoor unit which has the earliest Main address.
❈ Max. 16 indoor units can be connected.
Indoor unit
Indoor unit
Indoor unit
Outdoor unit

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dvm plus iii hrMini dvm

Table of Contents