05-3_control systems(082~141)
Control Systems
3
Integrated management system
3
3-1. DMS (Data Management Server)
(7) Option switch
DIP switch (SW03) : Use only for external contact signal control.
Pattern
1
2
3
4
Pattern 2
Option switch
Short external contact : Emergency stop
• Turns off all the indoor units when there is an ON signal input.
• All the remote control use is disabled.
• DMS will ignore any request from the upper-layer controllers.
• Schedule control is disabled temporarily.
Open external contact : Resume operation
• After Emergency stop, the indoor units stay in the current OFF states.
• All the remote control use is restored to the previous state.
• Schedule control is enabled again.
V-88
3/6/08 14:03
Page 88
DIP switch no.
1
2
3
4
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
No function
DI-2
DI-1
External contact
(Level-triggered)
Control details
No function (Default setting)
1. Emergency stop / Resume operation
Additional functions are temporarily disabled
under Emergency stop.
1. Indoor unit ON/OFF control
2. Permitted/Prohibited remote control use
Additional functions are not interrupted.
1. Indoor unit ON/OFF control
Additional functions are not interrupted.
Contact input
Not applied
Level-triggered
Level-triggered
Pulse-triggered