6.0

Additional information

6.1
Rod-out operation
The Rosemount 9295 Process Flow Meter is designed to accommodate a right
angle (90°) rod-out tool with 1/2" NPT connection. Straight rod-out tools may
need a nipple extension installed in order to provide clearance for the
transmitter housing.
Follow site-specific safety procedures when performing the rod-out operation.
6.2
Replacing the RTD
RTD replacement can be performed online as the assembly is not pressure
containing. Refer to the RTD Quick Start Guide for more information.
Figure 18. Replacing the RTD
6.3
Insulation recommendations
To protect the transmitter electronics and ensure an accurate temperature
measurement (when applicable), it is recommended that the meter body be
covered with 4 in. (100 mm) of insulation up to the bottom of the valve bodies.
Do not insulate the valves, uppers impulse lines, manifold or transmitter.
Insulation could lead to overheating and premature failure of the electronics.
Quick Start Guide
15