Oelay OutputsE: Oelay Settings
Use this menu to change the relay settings for the respective relay mode�
1� Navigate to SETUP > ADVANCED SETUP > RELAY OUTPUTS�
2� Press UP/DOWN to scroll to the applicable relay setting, then press ENTEO�
3� Scroll to and edit each option, as necessary�
N
OTEE:
Alarm icons "R1" and "R2" will appear in the upper right section of the
Home Screen to provide a local indication when a relay condition has been
met and when the relay has be energized�
Output Mode Option
OUTPUT SOURCE Parameter assignment (e�g� Flow Total)
SCALING
FACTOR
TOTALIZER
UNITS
PULSE WIDTH
OUTPUT SOURCE Parameter assignment (such as Flow Rate)
HIGH SETPOINT
HYSTERESIS HI
ALARM: HIGH
SET DELAY
RELEASE DELAY
LATCHING
OUTPUT SOURCE Parameter assignment (such as Flow Rate)
LOW SETPOINT
HYSTERESIS LO
ALARM: LOW
SET DELAY
RELEASE DELAY
LATCHING
April 2019
Description
Pulse(s) transmitted per unit of measure
Converts output unit of measure
Time between the rising and falling edges of a single pulse
Instructs the device to energize the relay if this value reached/
exceeded� This value is linked to the OUTPUT SOURCE and its
unit of measure (for example, Flow Rate in GPM)
Creates a window/zone below the HIGH SETPOINT value where
the relay remains in an energized state
Time in seconds that will elapse before the relay energizes, if
the HIGH SETPOINT value is reached/exceeded
Time in seconds that the relay will remain energized, if the
HYSTERESIS HI value is reached/exceeded
Leaves the relay in an energized state until it is manually cleared
on the device, either through the keypad interface or through
the Digital I/O channels
Instructs the device to energize the relay if this value reached/
exceeded� This value is linked to the OUTPUT SOURCE and its
unit of measure (for example, Flow Rate in GPM)
Creates a window/zone above the LOW SETPOINT value where
the relay remains in an energized state
Time in seconds that will elapse before the relay energizes, if
the LOW SETPOINT value is reached/exceeded
Time in seconds that the relay will remain energized, if the
HYSTERESIS LO value is reached/exceeded
Leaves relay in an energized state until it is manually cleared on
the device, either through the keypad interface or through the
Digital I/O channels
CTL-UM-02765-EN-01