Advanced Setup
b� Analog output options are:
Option
OUTPUT SOURCE
ANALOG FULL SCALE
ANALOG LOW SCALE
Oelay OutputsE: Oelay Mode
Use this menu to change the mode of one or both relay outputs� The mode
defines the behavior of the output�
1� Navigate to SETUP > ADVANCED SETUP > RELAY OUTPUTS.
2� Press UP/DOWN to scroll to an output mode, then press ENTEO�
3� Scroll through the available modes, then press ENTEO to select and save
the setting�
Option
NO RELAY/DISABLED
TOTALIZER
ALARM: HIGH
ALARM: LOW
ALARM: RANGE
MANUAL
Page 32
Description
Parameter assignment of the output (such as rate or total)
Maximum value associated with output maximum
Minimum value associated with output minimum
Table 17: Analog output settings
Description
Disables output
Totalizer output
On/Off function, energized at the high set point
On/Off function, energized at the low set point
On/Off function, energized beyond high and low set points
On/Off function of manual operation
Table 18: Relay mode options