Set Read Timeout
The Read Timeout is the maximum time allowed for the decode. The NJ/NX controller project has the Read
Timeout set to 2,000 milliseconds by default. This default value is defined by the value entered in the Initial Value
field for the HMI_ReadTimeout variable. This variable can be changed at runtime by the operator using the HMI
user interface. To aid in the setting of this variable, the last read time is accessible by monitoring the ReadTime
variable via the HMI or watching this value in SYSMAC Studio.
Set Read Timeout using the HMI
21.
Set Read Timeout using the HMI
21.1.
Run products with barcodes past the readers at production rates.
21.2.
Watch the Read Time value on the HMI and note the longest read time that was reported. In the image
below, the last decode had a read time of 860 milliseconds.
21.3.
Tap the Read Timeout numeric value and an on-screen keypad will be displayed as shown below.
Enter a value higher than the longest read time and press Enter. This value will be used until modified by
the user or a power cycle occurs. On a power cycle the Read Cycle will return to the value in the
Initial Value field in SYSMAC Studio.