Omron MicroHAWK ID-40 Technical Note page 10

360 barcode reading to omron nj/nx controller

Advertisement

Technical Note: MicroHAWK ID-40 360
4.10.
Apply power to the power supplies powering the NJ/NX controller and NA HMI Panel.
4.11.
Wait approximately 30 seconds for these components to fully power up.
4.12.
At this point all components should be powered and connected to the Ethernet switch. Confirm that
network activity is seen from the NJ/NX controller, the NA HMI Panel, and the six ID-40 readers.
4.13.
Confirm that the sensor signal is seen by the input module. If an object is moved slowly through the
sensor path, the input bit 00 indicator should toggle on and off. The image on the left below shows
input bit 00 = TRUE (ON) for the NX-ID5142-1 (NJ controller – configuration 1) and the image on the right
shows input bit 00 = TRUE (ON) for the NX1P2 (configuration 2).
Import Project into SYSMAC Studio
5. Import Project into SYSMAC Studio
5.1.
At the SYSMAC Studio start page, select Import... as shown below.
5.2.
Select the SYSMAC import file that matches the hardware configuration provided in the
Job_Files folder, shown below. For an NJ controller (configuration 1), select the file, "6_ID40_NJ301_
EIP_with_HMI_revC.smc2". For an NX1P2 (configuration 2) select the file, "6_ID40_NX1P2_EIP_with_HMI_
revC.smc2". Once the appropriate file is selected, click "Open".
10
Barcode Reading Solution
º
TECHNICAL
NOTE