Component Control During Heating Operation - Midea V6-i Series Service Manual

Commercial air conditioners
Hide thumbs Also See for V6-i Series:
Table of Contents

Advertisement

Table 3-5.2: Component control during heating operation
Component
diagram
Inverter compressor A
COMP(A)
Inverter compressor B
COMP(B)
DC fan motor A
DC fan motor B
Electronic
expansion
valve A
Electronic
expansion
valve C
Four-way valve
Solenoid
valve
(oil
balance)
Solenoid
valve
(fast
defrosting (in cooling)
and
unloading
(in
heating))
Solenoid
valve
(EXV
bypass)
Solenoid valve (indoor
units bypass)
Solenoid valve (inverter
compressor
A
vapor
injection)
Solenoid valve (inverter
compressor
B
vapor
injection)
Solenoid valve (inverter
compressor B pressure
balance)
Wiring
8-12HP
14-18HP
label
FANA
FANB
EXVA
EXVC
ST1
SV4
SV5
SV6
SV7
SV8A
SV8B
SV9
20-24HP
26-28HP
30-32HP
V6-i VRF 50/60Hz
Control functions and states
Controlled according to load requirement
Controlled according to outdoor ambient
temperature, outdoor heat exchanger pipe
temperature, discharge pressure and load
requirement
Position (steps) from 0 (fully closed) to 480
or 3000 (fully open), controlled according to
discharge superheat
Position (steps) from 0 (fully closed) to 480
(fully
open),
controlled
temperature different between plate heat
exchanger inlet and outlet
On
Open regularly
Controlled
according
to
temperature, discharge pressure, discharge
temperature,
compressor
frequency and discharge superheat
Off
Controlled according to load requirement
Controlled according to inverter compressor
A on/off
Controlled according to inverter compressor
B on/off
Open before compressor B startup and close
after compressor B running for 15 seconds.
Open after compressor B stop 10 seconds
and keep open 60 seconds.
according
to
ambient
running
39