E5: Abnormal Power Supply Voltage - Midea V6-i Series Service Manual

Commercial air conditioners
Hide thumbs Also See for V6-i Series:
Table of Contents

Advertisement

V6-i VRF 50/60Hz

2.5 E5: Abnormal power supply voltage

2.5.1
Digital display output
2.5.2
Description
 Abnormal power supply voltage.
 All units stop running.
 Error code is only displayed on the unit with the error.
2.5.3
Trigger / recover condition
 Trigger condition: Outdoor unit power supply phase voltage < 165V.
 Recover condition: Outdoor unit power supply phase voltage is > 180V.
 Reset method: Resume automatically.
2.5.4
Possible causes
 Outdoor unit power supply voltage is abnormal or a phase is missing.
 Loosened wiring within electric control box.
 High voltage circuit error.
 Main PCB damaged.