2.10.5
Procedure
Temperature sensor connection on main
Temperature sensor has short-circuited
Replace outdoor main PCB
Notes:
1.
Plate heat exchanger cooling refrigerant inlet temperature sensor (T6A) and plate heat exchanger cooling refrigerant outlet temperature sensor (T6B)
connection are port CN8 and CN8_1 on the main PCB (labeled 10 and 12, respectively, in Figure 5-2.1 in Part 5, 2.1 "Ports").
2.
Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor's resistance
characteristics table, the sensor has failed. Refer to Table 6-3.1 in Part 6, 3.1 "Temperature Sensor Resistance Characteristics".
F3 / F5
1
PCB is loose
No
2
or failed
No
Yes
Ensure the sensor is connected properly
Yes
Replace the sensor
V6-i VRF 50/60Hz