Midea V6-i Series Service Manual page 102

Commercial air conditioners
Hide thumbs Also See for V6-i Series:
Table of Contents

Advertisement

2.13.11
L8: Compressor frequency variation greater than 15Hz within one second protection
L9: Actual compressor frequency differs from target frequency by more than 15Hz protection
Disconnect the
power supply
The compressor has less than 12 hours
board, restart the unit and the error is
L8 protection
ODU stop valves are closed
No
Compressor wiring is not properly
No
The resistance between 3 phases of
compressor is over 5Ω
No
The insulation resistance of
compressor is less than 100Ω
preheating before initial operating
No
Replace the compressor inverter
solved
No
Refer to P1 or P3 troubleshooting
L9 protection
Yes
Yes
Yes
Yes
Yes
Yes
V6-i VRF 50/60Hz
Open the ODU stop valves
Reconnect the cables based on
wiring diagram
Replace the compressor
Ensure enough preheating time
Normal
101