2.13.8

L2: DC bus high voltage protection

L2 protection
The power supply is abnormal
No
The DC bus voltage (P, N) is abnormal
No
Replace the inverter module
Note:
1.
The normal DC voltage between terminals P and N on inverter module should be 450-650V. When the voltage is higher than 700V, L2
protection will be appeared.
98
Yes
Check the power supply