V6-i VRF 50/60Hz
2.7 E8: Outdoor unit address error
2.7.1
Digital display output
2.7.2
Description
Outdoor unit address error.
All units stop running.
Error code is only displayed on the unit with the error.
2.7.3
Trigger / recover condition
Trigger condition: Outdoor unit address is set more than 3.
Recover condition: Outdoor unit addresses are set from 0 to 3.
Reset method: Manually restart.
2.7.4
Possible causes
Invalid outdoor unit address.
Main PCB damaged.
82