Midea V6-i Series Service Manual page 117

Commercial air conditioners
Hide thumbs Also See for V6-i Series:
Table of Contents

Advertisement

V6-i VRF 50/60Hz
Insufficient refrigerant caused by
refrigerant leakage
The system is blocked, caused by crushed
or bent pipe, blocked EXV or dirty filter
The indoor load is too large
System contains air or nitrogen
The condenser heat exchange is poor
Replace outdoor main PCB
Notes:
1.
Compressor top temperature sensor and discharge pipe temperature sensor connections are ports CN4 and CN5 on the main PCB (labeled 3 and 4,
respectively, in Figure 5-2.1 in Part 5, 2.1 "Ports"). The discharge temperature switch connection is port CN19 on the main PCB (labeled 2 in Figure 5-2.1 in
Part 5, 2.1 "Ports").
2.
Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor's resistance
characteristics table, the sensor has failed. Refer to Table 6-3.2 in Part 6, 3.1 "Temperature Sensor Resistance Characteristics".
3.
An insufficiency of refrigerant causes compressor discharge temperature to be higher than normal, discharge and suction pressures to be lower than
normal and compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. These issues disappear once sufficient
refrigerant has been charged into the system. For normal system parameters refer to Table 6-3.4 and 6-3.5 in Part 6, 3.2 "Normal Operating Parameters of
Refrigerant System".
4.
A low pressure side blockage causes compressor discharge temperature to be higher than normal, suction pressure to be lower than normal and
compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. For normal system parameters refer to Table 6-3.4 and
6-3.5 in Part 6, 3.2 "Normal Operating Parameters of Refrigerant System".
5.
An indoor load that is too large causes suction and discharge temperatures to be higher than normal. For normal system parameters refer to Table 6-3.4
and 6-3.5 in Part 6, 3.2 "Normal Operating Parameters of Refrigerant System".
6.
Air or nitrogen in the system causes discharge temperature to be higher than normal, discharge pressure to be higher than normal, compressor current to
be higher than normal, abnormal compressor noise and an unsteady pressure meter reading. For normal system parameters refer to Table 6-3.4 and 6-3.5
in Part 6, 3.2 "Normal Operating Parameters of Refrigerant System".
7.
In cooling mode check outdoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check indoor heat exchangers, fans and air outlets
for dirt/blockages.
116
3
No
4
No
5
No
6
No
7
No
Add refrigerant and inspect the system
Yes
for leaks
Inspect the system and fix the error. If the
Yes
filter is blocked by ice, the piping should
be cleaned
Make sure the combination ratio is less
Yes
than 130%
Flush all refrigerant then vacuum the
Yes
system and recharge refrigerant. Add oil
to the system if it leaks
Yes
Inspect the system and fix the error

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents