2.11 F6: Electronic expansion valve connection error

2.11.1
Digital display output
2.11.2
Description
 Electronic expansion valve connection error.
 All units stop running.
 Error code is only displayed on the unit with the error.
2.11.3
Trigger / recover condition
 Trigger condition: The main control board cannot receive the feedback signal of EXV.
 Recover condition: The main control board can receive the feedback signal of EXV.
 Reset method: When the main control board can receive the feedback signal of EXV, F6 flashes, a manual system
restart id required before the system can resume operation.
2.11.4
Possible causes
 Electronic expansion valve coil not connected properly or has malfunctioned.
 Damaged main PCB.