Setting range: 15 – 70 °C
Default value:
temp. period 1
temp. period 2
temp. period 3
temp. period 4
temp. period 5
temp. period 6
temp. period 7
Set the function for under floor drying here.
You can set up to seven period times with different
calculated flow temperatures. If less than seven periods
are to be used, set the remaining period times to 0 days.
Mark the active window to activate the underfloor drying
function. A counter at the bottom shows the number of
days the function has been active.
TIP
If operating mode "add. heat only" is to be used,
select it in menu 4.2.
TIP
It is possible to save a floor drying log that
shows when the concrete slab has reached
the correct temperature. See section
floor
drying" on page 59.
MENU 5.10 - CHANGE LOG
Read off any previous changes to the control system
here.
The date, time and ID no. (unique to certain settings)
and the new set value is shown for every change.
Caution
The change log is saved at restart and remains
unchanged after factory setting.
MENU 5.11 - SLAVE SETTINGS
Settings for installed slaves can be made in the sub
menus.
MENU 5.11.1 - EB101 - 5.11.8 - EB108
Make settings for the installed slaves here.
MENU 5.11.1.1 - HEAT PUMP
Make settings for the installed slave here. To see what
settings you can make, see installation manual for the
relevant installed slave.
54
Chapter 8 | Control
MENU 5.11.1.2 - CHARGE PUMP (GP12)
op. mode
20 °C
Heating/cooling
30 °C
Setting range: auto / intermittent
40 °C
45 C
Default value: intermittent
40 °C
30 °C
Set the operating mode for the charge pump here.
20 °C
auto: The charge pump runs according to the current
operating mode for SMO 40.
intermittent: The charge pump starts and stops 20
seconds before, and after, the compressor in the heat
pump.
speed during operation
heating, hot water, pool, cooling
Setting range: auto / manual
Default value: auto
Manual setting
Setting range: 1–100 %
Default values: 70 %
min. allowed speed
Setting range: 1–100 %
Default values: 1 %
"Logging
speed in wait mode
Setting range: 1–100 %
Default values: 30 %
max. allowed speed
Setting range: 80–100 %
Default values: 100 %
Set the speed at which the charge pump is to operate
in the present operating mode. Select "auto" if the speed
of the charge pump is to be regulated automatically
(factory setting) for optimal operation.
If "auto" is activated for heating operation, you can also
make the setting "min. allowed speed" and "max. allowed
speed", which restricts the charge pump and prevents
it from running at a lower or higher speed than the set
value.
For manual operation of the charge pump, deactivate
"auto" for the current operating mode and set the value
to between 1 and 100% (the previously set value for
"max. allowed speed" and "min. allowed speed" no longer
applies).
Speed in wait mode (only used if "auto" has been selec-
ted for "Operating mode") means the charge pump oper-
ates at the set speed during the time when neither
compressor operation nor additional heat are required.
NIBE SMO 40