MENU 5.3.14 - F135
charge pump speed
Setting range: 1 – 100 %
Factory setting: 70 %
hot water at cooling
Setting range: on/off
Factory setting: off
Here you can set the charge pump speed for F135. You
can also choose whether you want to be able to charge
hot water with F135 at the same time as the outdoor
module produces cooling.
Caution
It is necessary for "active cooling 4 pipe" to
be selected in either "accessories" or "soft
in/outputs" to enable activation of "hot water
during cooling". The heat pump must also be
activated for cooling operation.
MENU 5.3.15 - GBM COMMUNICATION
MODULE
start diff additional heat
Setting range: 10 – 2,000 DM
Factory setting: 700 DM
hysteresis
Setting range: 10 – 2,000 DM
Factory setting: 100 DM
Make settings for the gas boiler GBM 10-15 here. For
example . you can select when the gas boiler is to start.
See the accessory installation instructions for a descrip-
tion of function.
MENU 5.3.16 - HUMIDITY SENSOR
climate system 1 HTS
Setting range: 1–4
Default value: 1
limit RH in the room, syst.
Setting range: on/off
Factory setting: off
prevent condensation, syst.
Setting range: on/off
Factory setting: off
limit RH in the room, syst.
Setting range: on/off
Factory setting: off
52
Chapter 8 | Control
Up to four humidity sensors (HTS 40) can be installed.
Here you select whether your system(s) is/are to limit
the relative humidity level (RH) during heating or cooling
operation.
You can also choose to limit min. cooling supply and
calculated cooling supply to prevent condensation on
pipes and components in the cooling system.
See the Installer Manual for HTS 40 for function descrip-
tion.