Nibe SMO 40 Installer Manual page 25

Control module
Hide thumbs Also See for SMO 40:
Table of Contents

Advertisement

OUTSIDE SENSOR
Install the outdoor temperature sensor (BT1) in the
shade on a wall facing north or north-west, so it is unaf-
fected by the morning sun for example.
Connect the sensor to terminal block X6:1 and X6:2 on
the input board (AA3). Use a twin core cable with a cable
area of at least 0.5 mm².
If a conduit is used it must be sealed to prevent condens-
ation in the sensor capsule.
1 2
3
4
L N
1
1
0
PE
2
3 4
AA3-X6
LEK
NIBE SMO 40
SMO Externt
SMO 40
External
1
2
3
BT1
4
5
6
7
8
AA3-X6
ROOM SENSOR
SMO 40 comes with a room sensor (BT50). The room
sensor has a number of functions:
Shows current room temperature in the control
1.
module display.
2.
Provides the option of changing the room temperat-
ure in °C.
3.
Provides the option of fine-tuning the room temper-
ature.
Install the sensor in a neutral position where the set
temperature is required. A suitable location is on a free
inner wall in a hall approx. 1.5 m above the floor. It is
important that the sensor is not prevented from meas-
uring the correct room temperature by being located,
for example, in a recess, between shelves, behind a
curtain, above or close to a heat source, in a draft from
an external door or in direct sunlight. Closed radiator
thermostats can also cause problems.
The control module operates without the sensor, but if
you want to read off the home's indoor temperature in
the control module's display, the sensor must be in-
stalled. Connect the room sensor to terminal block X6:3
and X6:4 on the input board (AA3).
If the sensor is to be used to change the room temper-
ature in °C and/or to fine-tune the room temperature,
the sensor must be activated in menu 1.9.4.
If the room sensor is used in a room with underfloor
heating, it should only have an indicatory function, not
control of the room temperature.
1 2
3
4
L N
1
1
0
PE
2
3 4
AA3-X6
LEK
Caution
Changes of temperature in accommodation
take time. For example, short time periods in
combination with underfloor heating will not
give a noticeable difference in room temperat-
ure.
Chapter 5 | Electrical connections
SMO Externt
SMO 40
External
2
3
4
5
6
BT50
7
8
9
AA3-X6
25