MENU 5.1.25 - TIME FILTER ALARM
months btwn filter alarms
Setting range: 1 – 24
Factory setting: 3
Here you set the number of months between alarms
for a reminder to clean the filter in a connected access-
ory.
MENU 5.2 - SYSTEM SETTINGS
Make different system settings for your installation here,
e.g. activate connected slaves and which accessories
are installed.
MENU 5.2.2 - INSTALLED SLAVES
If one or more air/water heat pumps are connected to
the control module, you set it here.
There are two ways of activating connected slaves. You
can either mark the alternative in the list or use the
automatic function "search installed slaves".
search installed slaves
Mark "search installed slaves" and press the OK button
to automatically find connected slaves for the master
heat pump.
MENU 5.2.3 - DOCKING
Enter how your system is docked regarding pipes, for
example to pool heating, hot water heating and heating
the building.
This menu has a docking memory which means that the
control system remembers how a particular reversing
valve is docked and automatically enters the correct
docking the next time you use the same reversing valve.
Slave (heat pump)
slave 1
s2
s3 s4 s5 s6 s7 s8
Compressor
Slave: Here you select the heat pump for which the
docking setting is to be adjusted.
48
Chapter 8 | Control
Workspace for docking
docking5.2.3
Marking frame
Compressor: Here, you select whether the compressor
in the heat pump is blocked (factory setting) or standard
(docked, for example, to pool heating, hot water charging
and heating the building).
Marking frame: Move around the marking frame using
the control knob. Use the OK button to select what you
want to change and to confirm the setting in the options
box that appears to the right.
Workspace for docking: The system docking is drawn
here.
Symbol
Description
Compressor (blocked)
Compressor (standard)
Reversing valves for hot water, cooling respect-
ively pool control.
The designations above the reversing valve
indicate where it is electrically connected
(EB101 = Slave 1, CL11 = Pool 1 etc.).
Hot water charging
Pool 1
Pool 2
Heating (heating the building, includes any
extra climate system)
Cooling
MENU 5.2.4 - ACCESSORIES
Set which accessories are installed on the installation
here.
If the water heater is connected to SMO 40 hot water
charging must be activated here.
There are two ways of activating connected accessories.
You can either mark the alternative in the list or use the
automatic function "search installed acc.".
search installed acc.
Mark "search installed acc." and press the OK button to
automatically find connected accessories for SMO 40.
MENU 5.3 - ACCESSORY SETTINGS
The operating settings for accessories that are installed
and activated are made in the sub-menus for this.