Commissioning

6
Commissioning
6.1

Commissioning requirement

To commission the device, a PC with ETS is required along with a connection to the ABB i-bus
KNX interface.
Once the bus and auxiliary voltages are connected, the device is ready for operation.
6.2

Commissioning overview

The ABA/S 1.2.1 Logic Controller is commissioned using the Logic Controller/* application.
* ... = Current version number of the application. Please refer to the software information on our
homepage for this.
ETS is required in order to parametrize the device.
For information on how to use the i-bus
6.3

Assignment of the physical address

The physical address, group address and parameters are assigned and programmed in ETS.
The device features a Programming button for physical address assignment. The red Programming LED
lights up after the button has been pressed. It goes off once ETS has assigned the physical address or the
Programming button is pressed again.
The device performs an ETS reset during physical address programming. This resets all states.
Note
®
Tool, see 4.5
Integration in the i-bus® Tool
®