ABB i-bus KNX ABA/S 1.2.1 Product Manual page 73

Logic controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Function
Input receives a 1 (true):
o
o
Input receives a 0 (false):
o
o
If the timer reaches the On-time:
o
o
Retrigger:
If Retrigger = 1 (true):
o
If Retrigger = 0 (false):
o
Exception handling
If the On-time input is unlinked, the element uses 00:00:30.
If the On-time input is negative, the element uses 00:00:00.
If the On-time input has a value of 00:00:00, the output is always 0.
Bus voltage failure, download and restart
The internal timer value is saved. This value is restored on restart.
Output = 1 (true)
Timer restarts
Output = 0 (false)
Timer stops
Output = 0 (false)
Timer stops
When the input receives a 1 the timer restarts
If the timer is running and the input receives a 1 (true) it ignores it. The timer continues running.
ABA/S 1.2.1 | 2CDC509086D0201 73