ABB i-bus KNX ABA/S 1.2.1 Product Manual page 42

Logic controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Description of parameters
Change in %:
The value change is defined as follows:
(NEW_VALUE – LAST_SENT_VALUE) / LAST_SENT_VALUE
If NEW_VALUE = LAST_SENT_VALUE = 0, result is 0%
If NEW_VALUE <> 0 and LAST_SENT_VALUE = 0, result is 100%
Function
Whenever a telegram is received the output starts a recalculation independently if the value has changed.
Bus voltage failure, download and restart
The output values are not saved. Cyclic sending starts once the output receives a valid value.
Output values that cannot be sent on the bus (e.g. due to bus load or bus voltage failure) are overwritten
by newer values.
Element display
Element name
First group address
Data widths (1 bit, 2 bits, 4 bits, 1 byte, 2 bytes, 4 bytes, date, time, date/time, color)
The first group address is the one that sends a value. The group addresses are displayed in the same
layout as in ETS (e.g. 2-level or 3-level).
Datapoint Type
Select the datapoint type required for displaying the value on the KNX accordingly.
All assigned group addresses are listed in Data Types in the Properties window. They cannot be changed
(read-only).
42 2CDC509086D0201 | ABA/S 1.2.1