Subtraction (Sub) - ABB i-bus KNX ABA/S 1.2.1 Product Manual

Logic controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.10.23

Subtraction (SUB)

Description
Subtracts one input value (Subtrahend) from another (Minuend).
Inputs
No.
1
2
Outputs
No.
1
2
Parameters
None
Function
Whenever a telegram is received the output starts a recalculation independently if the value has changed.
An overflow will occur if the
If the
o
o
If the
o
o
If the
o
o
Other
Unlinked inputs are treated as if they did not exist and are set to 0.
DPT
Abbr.
8 bit or higher
M
Same as Input 1
S
DPT
Abbr.
Same as Input 1
D
1 bit
Ov
Subtraction
Subtraction
value is greater than the maximum DPT value:
D = 0
Ov = 1 (true)
Subtraction
value is less than the minimum DPT value:
D = 0
Ov = 1 (true)
Subtraction
value is within the valid range of the DPT:
D = Difference between the two input values (Minuend - Subtrahend)
Ov = 0 (false)
Name
Visible
Minuend
Always
Subtrahend
Always
Name
Visible
Difference
Always
Overflow
Always
value is outside the DPT range:
Description
Description
Indicates an overflow
ABA/S 1.2.1 | 2CDC509086D0201 67