9. Rosemount 2088/2090 sensor module must be securely screwed in
place to maintain the ingress protection of the enclosure.
10. Some variants of the equipment have reduced markings on the
nameplate. Refer to the Certificate for full equipment marking.
I1 ATEX Intrinsic Safety and Dust
Certificate
Standards
Markings
Table 4-4: Input Parameters
Parameters
Voltage U
i
Current I
i
Power P
i
Capacitance C
Inductance L
Special Conditions for Safe Use (X):
1. When fitted with a transient suppression terminal block, the
equipment is not capable of withstanding the 500 V insulation test.
This must be taken into account during installation.
2. The enclosure may be made of aluminium alloy and given a protective
polyurethane paint finish; however, care should be taken to protect it
from impact or abrasion if located in a Zone 0 area.
N1 ATEX Type n and Dust
Certificate BAS00ATEX3167X; BAS01ATEX1427X
Standards EN60079-0:2012, EN60079-15:2010, EN60079-31:2009
Markings
Special Conditions for Safe Use (X):
1. This apparatus is not capable of withstanding the 500 V insulation test
that is required by EN60079-15. This must be taken into account when
installing the apparatus.
Quick Start Guide
BAS00ATEX1166X
EN60079-0:2012+A11:2013,EN60079-11:2012
II 1 G Ex ia IIC T4 Ga (–55 °C ≤ T
HART
30 V
200 mA
0.9 W
0.012 µF
i
0 mH
i
II 3 G Ex nA IIC T5 Gc (–40 °C ≤ T
IIIC T50 °C T
60 °C Da
500
Quick Start Guide
≤ +70 °C)
a
≤ +70 °C);
II 1 D Ex t
a
29