Quick Start Guide
Table 4-3: Input
Parameters (continued)
Voltage U
i
Current I
i
Power P
i
Capacitance C
Inductance L
Special Conditions for Safe Use (X)
1. The equipment is not capable of withstanding the 500V insulation test
required by clause 6.3.13 of IEC60079-11:2011. This must be taken
into account when installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however, care should be taken to protect it
from impact or abrasion if located in Zone 0.
N7 IECEx Type n
Certificate
Standards
Markings
Special Condition for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V insulation test
required by IEC60079-15. This must be taken into account when
installing the apparatus.
China
E3 China Flameproof
Certificate
Standards
Markings
Special Conditions for Safe Use (X):
1. The relation between ambient temperature range and temperature
class is as follows:
T
a
–50
24
30 V
200 mA
0.9 W
0.012 µF
i
0 mH
i
IECEx BAS 12.0108X
IEC60079-0:2011, IEC60079-15:2010
Ex nA IIC T5 Gc (–40 °C ≤ T
GYJ18.1023X
GB3836.1-2010, GB3836.2-2010, GB3836.20-2010
Ex d IIC T6/T5 Ga/Gb
Temperature class
+70 °C
T5
~
≤ +70 °C)
a
Emerson.com/Rosemount
February 2019