Siemens SINAMICS G130 Operating Instructions Manual page 31

Cabinet design and emc
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

NOTICE
Device failure due to air short-circuit in the control cabinet
Unsuitable air guidance can cause an air short-circuit, which can result in overheating in the
control cabinet and device failure.
• Install suitable barriers in the control cabinet in order to prevent an air short-circuit from
Barriers must be installed in such a way that no air can flow along the outer sides on the top
and bottom of the devices. In particular, air must be prevented from flowing from the top
(warm discharged air) to the bottom (cold cooling air). Suitable plates can be used as
barriers and must extend to the side panels or cabinet doors. They must be set up in such a
way that the outgoing air current is not forced into the cabinet cross-beams but is instead
diverted around them. Barriers must be in place for all degrees of protection higher than
IP20.
The cabinets adjacent to the converter cabinets must also be taken into account when
barriers are installed.
To ensure sufficient ventilation for the devices, the opening cross-sections (minimum values)
specified in the following table must be observed.
The specified opening cross-sections comprise several small openings. To ensure that
pressure loss is kept to a minimum and that the flow resistance does not become too great
at these mesh-type openings, the cross sectional area of each opening must be around at
least 190 mm² (e.g. 7.5 mm x 25 mm or 9.5 mm x 20 mm).
To ensure that the devices operate continuously, suitable measures must be taken to
prevent the ingress of dirt and dust. Wire lattices (wire fabric DIN 4189-St-vzk-1x0.28) or
filter mats (min. filter class G2) must be used for this purpose. The choice of filter mats
depends on the required degree of protection and the ambient conditions. If cabinets are
installed in an environment containing fine dust particles or oil vapors, micro-filter mats must
be used to prevent the devices from becoming contaminated.
If dirt filters are used, the specified opening cross-sections and the filter areas must be
adjusted upwards.
NOTICE
Device failure due to overheating as a result of contaminated dirt filters
Contaminated filter mats cause the device to overheat and fail.
• If dirt filters are used, observe the specified replacement intervals.
If the filter mats are heavily contaminated, the volume of air drawn is reduced due to the
increased flow resistance. This can cause the fans integrated in the devices to overload, or it
could cause the devices themselves to overheat and become damaged.
Cabinet design and EMC
Operating Instructions, 07/2016, A5E00427629A
occurring.
Cabinet air conditioning
5.2 Ventilation
31