JX3-BN-ETH
Internal
Publish/Subscribe
Management
Jetter AG
Select "Network" from the hardware tree and open the context menu by
rightclicking with the mouse. Here, click menu item "Download all
Configurations".
Result:
The controller and the bus node have received the configuration data.
If you make any changes to bus node or controller hardware, you have to
send the current configuration to the connected hardware components via
Hardware Manager.
If you click in Hardware Manager "Send Configuration", the following happens:
In the JetSym project a directory (e.g. Release) has been created below the
active configuration. This directory contains the following files:
ModConfig.da
ModConfig_BN_001.da
NetConsistency.xml
Publisher.pub
Publisher_BN_001.pub
Subscriber.sub
Subscriber_BN_001.sub
The following files are copied to the local controller (with the Global Node
Number 000).
ModConfig.da
NetConsistency.xml
The following files are copied to the bus node JX3-BN-ETH:
Publisher.pub
Subscriber.sub
ModConfig.da
Jetter AG advises the use of JetSym Hardware Manager for this task.
Experienced users may also transfer these files via FTP (e.g. when the bus
node has been replaced), but we recommend to use the Hardware Manager.
Note:
Do not delete these files. They are required by JetSym, the controller, and
bus node.
If you delete, for instance, the file "ModConfig_BN_001.da", you are no longer
able to acces remote I/Os.