Page 1
User Manual JX3-THI2-TC-EI We automate your success.
Page 2
Revisions and further development of our products are not automatically mentioned in a reviewed document. Jetter AG shall not be liable for errors in form or content, or for missing updates, as well as for damages or disadvantages resulting from such failure.
Installing the expansion module on the DIN rail .............. 14 Removing the expansion module from the DIN rail............... 15 Dismounting the enclosure from the backplane module ............ 16 6 Electrical connection ........................ 17 Temperature inputs X41, X42 .................... 17 Connecting a thermocouple .................... 17 JX3-THI2-TC-EI User Manual...
Page 4
9 Maintenance and repairs ...................... 29 Maintenance, repairs and disposal.................. 29 Storage and shipment ...................... 29 10 Service ............................ 30 10.1 Customer service ........................ 30 11 Spare parts and accessories ....................... 31 11.1 Spare parts.......................... 31 11.2 Accessories ........................... 31 JX3-THI2-TC-EI User Manual...
For information on new revisions of this document, visit the download area on our website. This document is not subject to any updating service. Start | Jetter - We automate your success. For further information refer to the following information products: ■...
Low risk CAUTION Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. Material damage NOTICE Indicates a situation which, if not avoided, could result in malfunctions or material damage. JX3-THI2-TC-EI User Manual 6 / 34...
Product description | 3 3 Product description The JX3-THI2-TC-EI expansion module serves in combination with one of our controls for temperature measurement. It has 2 isolated thermocouple inputs that can be used with both, isolated and non-isolated sensors ("grounded junction"...
The sensor type has to be entered as number into register 1107 for channel # 1, and register 1207 for channel # 2. Thermocouple types Number Type B Type E Type J Type K Type N Type R Type S Type T Tab. 1: Connectable thermocouple types: JX3-THI2-TC-EI User Manual 8 / 34...
CE marking Hardware revision Type key 3.6 Scope of delivery Scope of delivery Item number Quantity JX3-THI2-TC-EI 10001063 Male connector in spring-cage technology, 60869252 10-pin Terminal labels 60870411 Keying pins 60870410 Installation manual 60880261 JX3-THI2-TC-EI User Manual 9 / 34...
Degree of pollution - Electronics Degree of pollution 2 DIN EN 61131-2 Usually, the pollution is non-conductive. However, temporary conductivity due to condensation may occur. Tab. 2: Environmental conditions JX3-THI2-TC-EI User Manual 10 / 34...
Tab. 5: Mechanical specifications 4.6 EMC values 4.6.1 Enclosure Electrical safety Parameter Values Standard Protection class DIN EN 61131-2 Dielectric test voltage Functional ground is connected to chassis ground internally. Overvoltage category Tab. 6: Electrical safety JX3-THI2-TC-EI User Manual 11 / 34...
DIN EN 61000-6-2 0.5 kV DIN EN 61000-4-5 Surge voltages, asymmetric, line to earth Common-mode interference tr/th 1.2/50 µs DIN EN 61131-2 DIN EN 61000-6-2 0.5 kV DIN EN 61000-4-5 Tab. 9: DC power supply inputs and outputs JX3-THI2-TC-EI User Manual 12 / 34...
Surge voltages, asymmetrical, line to earth: tr/th 1.2/50 µs DIN EN 61131-2 DIN EN 61000-6-2 Common-mode interference 1 kV DIN EN 61000-4-5 Common-mode interference 0.5 kV Tab. 10: Immunity of shielded data and I/O lines JX3-THI2-TC-EI User Manual 13 / 34...
Place the upper latch (2) in angled position on the DIN rail (1). Snap the lower latch of the device onto the lower edge of the DIN rail. Slide the device to its intended position. JX3-THI2-TC-EI User Manual 14 / 34...
DIN rail release latch Detail view Disconnect the system from the power supply. Remove the device from the mains. Pry the release latch (2) downwards and pull the device off the DIN rail (1). JX3-THI2-TC-EI User Manual 15 / 34...
Fig. 7: Dismounting the enclosure from the backplane module DIN rail latch Detail view Disconnect the system from the power supply. Press the upper and lower latches (1) on the device simultaneously. Keep the latches pressed and pull off the enclosure. JX3-THI2-TC-EI User Manual 16 / 34...
Bridge the connections I1+, U1- and 0 V at the module. Make sure there is a low-resistance connection and a low contact resistance at the bridges. Connect the thermocouple cable to the module. The following example shows the connection of a thermocouple to terminal X41. JX3-THI2-TC-EI User Manual 17 / 34...
Page 18
Connect the shield of the cable to one of the SHLD connectors of the corre- sponding terminal. SHLD 10 SHLD Connect the cable shield with the greatest possible surface area to a shielding terminal (A). JX3-THI2-TC-EI User Manual 18 / 34...
Our products offer a host of functions which can be accessed by the user via reg- isters. Every register has got an unambiguous number, the register number. Each digital input or output has got an unambiguous I/O number. JX3-THI2-TC-EI User Manual 19 / 34...
Description Value range Prefix 1 Fig. 12: Example: I/O numbers Bus node ID, GNN 001 … 199 Prefix 2 Position of the module within the 02 … 17 station Module-specific I/O number 01 … 16 JX3-THI2-TC-EI User Manual 20 / 34...
Type of access Read access Data type Float Value after reset Analog value of temperature input # 1 Default value The measured value is displayed in °C. The unit can be configured via Command registers JX3-THI2-TC-EI User Manual 22 / 34...
Displaying the temperature measured by the thermocouple at the measuring point Displaying the temperature measured by the thermocouple at the reference point on the module JX3-THI2-TC-EI User Manual 23 / 34...
1= Displaying the thermocouple temperature Bit 12 Calibration mode 0= Disabled 1= Enabled Bit 14 Channel enabled/disabled 0= Disabled 1= Enabled Bit 15 Reset 0= No reset/normal measuring mode 1= Initiating a reset (synchronously) JX3-THI2-TC-EI User Manual 24 / 34...
This function allows you to easily calibrate the module. Module register 9740 Oscilloscope function Type of access Read/write Value range 0 … 4 JX3-THI2-TC-EI User Manual 25 / 34...
Page 26
When the max- imum number is reached, the recording session stops. The maximum number of readings depends on the num- ber of channels which have been configured. Minimum sampling interval (read only) JX3-THI2-TC-EI User Manual 26 / 34...
°C, F Value after reset Module register 1y21 Storing the maximum value Description The module register stores the maximum value. Notation The value is scaled with a factor of 1,000. Example: 123,456 corresponding to 123.456 JX3-THI2-TC-EI User Manual 27 / 34...
100613 Hardware revision 100614 Hardware option Register values 100700 Revision of EDS page 1 100701 ... 100707 Serial number of the module 100708 Production date: Day 100709 Production date: Month 100710 Production date: Year JX3-THI2-TC-EI User Manual 28 / 34...
In case of damaged packaging inspect the device for any visible damage, and in- form your freight forwarder and the Jetter AG of the damage caused during ship- ment. If the device is damaged or has been dropped, it is strictly forbidden to use...
To contact them, please call our technical hotline or use the contact form on our homepage: Technical hotline | Jetter - We automate your success. You are also welcome to send an e-mail to our technical hotline: hotline@jetter.de...
Inadequate accessories might cause damage to the product NOTICE Parts and equipment from other manufacturers might impede the function of the device and cause damage to the product. ● Only use accessories recommended by Jetter AG. 11.1 Spare parts Component Item no.:...
Page 32
Example: System overview of a controller together with various expansion modules .... Fig. 9 Example: Register numbers ....................Fig. 10 Example: I/O numbers......................Fig. 11 Example: Register numbers ....................Fig. 12 Example: I/O numbers......................JX3-THI2-TC-EI User Manual 32 / 34...
Page 33
Tab. 5 Mechanical specifications......................Tab. 6 Electrical safety ........................Tab. 7 Emitted interference ........................ Tab. 8 Immunity to interference......................Tab. 9 DC power supply inputs and outputs..................Tab. 10 Immunity of shielded data and I/O lines .................. JX3-THI2-TC-EI User Manual 33 / 34...
Page 34
Jetter AG Graeterstrasse 2 71642 Ludwigsburg www.jetter.de E-mail info@jetter.de Phone +49 7141 2550-0 We automate your success.
Need help?
Do you have a question about the JX3-THI2-TC-EI and is the answer not in the manual?
Questions and answers