1MRK 511 358-UEN A
A resolution of 10 ms can be achieved when the settings are defined within the range
1.00 second ≤ tAlarm ≤ 99 999.99 seconds
1.00 second ≤ tWarning ≤ 99 999.99 seconds.
If the values are above this range the resolution becomes lower
99 999.99 seconds ≤ tAlarm ≤ 999 999.9 seconds
99 999.99 seconds≤ tWarning ≤ 999 999.9 seconds
The limit for the overflow supervision is fixed at 999999.9 seconds.
15.13
Comparator for integer inputs - INTCOMP
15.13.1
Identification
Function description
Comparison of integer values
15.13.2
Application
The function gives the possibility to monitor the level of integer values in the system relative
to each other or to a fixed value. It is a basic arithmetic function that can be used for
monitoring, supervision, interlocking and other logics.
15.13.3
Setting guidelines
For proper operation of comparison the set value should be set within the range of ± 2 ×10
Setting procedure on the IED:
EnaAbs : This setting is used to select the comparison type between signed and absolute
values.
Absolute : The function will do absolute comparison between input and reference value
•
Signed : The function will do signed comparison between input and reference value
•
RefSource : This setting is used to select the reference source between input and setting for
comparison.
REF : The function will take reference value from input REF
•
SetValue : The function will take reference value from setting SetValue
•
SetValue : This setting is used to set the reference value for comparison when setting
RefSource is selected as SetValue .
Application manual
Note that
tAlarm and tWarning are independent settings, that is, there is no
tAlarm > tWarning .
check if
IEC 61850
identification
INTCOMP
GUID-5992B0F2-FC1B-4838-9BAB-2D2542BB264D v1
IEC 60617
ANSI/IEEE C37.2
identification
device number
Int<=>
GUID-4C6D730D-BB1C-45F1-A719-1267234BF1B9 v1
GUID-ADA3E806-BEF1-4D15-B270-207386A0AEE4 v1
Section 15
Logic
9
.
371