Figure 198: Redundant station bus
18.2.6.3
Setting guidelines
Redundant communication (PRP) is configured in the local HMI under Main menu/
Configuration/Communication/Ethernet configuration/PRP
The settings are found in the Parameter Setting tool in PCM600 under IED Configuration/
Communication/Ethernet configuration/PRP. By default the settings are read only in the
Parameter Settings tool, but can be unlocked by right clicking the parameter and selecting
Lock/Unlock Parameter.
Operation : The redundant communication will be activated when this parameter is set to
On. After confirmation the IED will restart and the setting alternatives Rear OEM - Port AB and
CD will not be further displayed in the local HMI. The ETHLANAB and ETHLANCD in the
Parameter Setting Tool are irrelevant when the redundant communication is activated, only
PRP IPAdress and IPMask are valid.