Integer To Boolean 16 Conversion Ib16; Identification; Application - ABB Relion REC670 Applications Manual

Bay control version 2.1 iec
Hide thumbs Also See for Relion REC670:
Table of Contents

Advertisement

Section 15
Logic
Name of input
IN12
IN13
IN14
IN15
IN16
The sum of the numbers in column "Value when activated" when all INx (where 1≤x≤16) are
active that is=1; is 65535. 65535 is the highest boolean value that can be converted to an
integer by the BTIGAPC function block.
15.10

Integer to Boolean 16 conversion IB16

15.10.1

Identification

Function description
Integer to boolean 16 conversion
15.10.2

Application

Integer to boolean 16 conversion function (IB16) is used to transform an integer into a set of 16
binary (logical) signals. It can be used – for example, to connect integer output signals from
one function to binary (logical) inputs to another function. IB16 function does not have a
logical node mapping.
The Boolean 16 to integer conversion function (IB16) will transfer a combination of up to 16
binary inputs INx where 1≤x≤16 to an integer. Each INx represents a value according to the
table below from 0 to 32768. This follows the general formula: INx = 2
of all the values on the activated INx will be available on the output OUT as a sum of the values
of all the inputs INx that are activated. OUT is an integer. When all INx where 1≤x≤16 are
activated that is = Boolean 1 it corresponds to that integer 65535 is available on the output
OUT. IB16 function is designed for receiving up to 16 booleans input locally. If the BLOCK input
is activated, it will freeze the output at the last value.
Values of each of the different OUTx from function block IB16 for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output OUT on
the function block IB16.
Name of input
IN1
IN2
IN3
IN4
IN5
Table continues on next page
368
Type
Default
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
IEC 61850
identification
IB16
Type
Default
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
Description
Value when
activated
Input 12
2048
Input 13
4096
Input 14
8192
Input 15
16384
Input 16
32768
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
x-1
Description
Value when
activated
Input 1
1
Input 2
2
Input 3
4
Input 4
8
Input 5
16
1MRK 511 358-UEN A
Value when
deactivated
0
0
0
0
0
SEMOD158367-1 v2
SEMOD167941-2 v2
SEMOD158499-5 v4
where 1≤x≤16. The sum
Value when
deactivated
0
0
0
0
0
Application manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 670 series

Table of Contents