Relationships Between Setting Parameter Base Current, Ct Rated Primary Current And Minimum Pickup Of A Protection Ied - ABB Relion REC670 Applications Manual

Bay control version 2.1 iec
Hide thumbs Also See for Relion REC670:
Table of Contents

Advertisement

1MRK 511 358-UEN A
Protected Object
L1
L2
a)
b)
IEC11000029 V4 EN-US
Figure 18: Connections for single-phase CT input
Where:
1)
2)
3)
4)
4.2.3
Relationships between setting parameter Base Current, CT
rated primary current and minimum pickup of a protection IED
Note that for all line protection applications (e.g. distance protection or line differential
protection) the parameter Base Current (i.e. IBase setting in the IED) used by the relevant
protection function, shall always be set equal to the largest rated CT primary current among all
Application manual
L3
1
(+)
INS
(-)
(+)
INS
(-)
shows how to connect single-phase CT input in the IED.
is TRM where these current inputs are located. It shall be noted that for all these current inputs
the following setting values shall be entered.
For connection (a) shown in figure 18:
CT prim = 1000 A
CT sec = 1A
CTStarPoint = ToObject
For connection (b) shown in figure 18:
CT prim = 1000 A
CT sec = 1A
CTStarPoint = FromObject
shows the connection made in SMT tool, which connect this CT input to the fourth input channel
of the preprocessing function block 4).
is a Preprocessing block that has the task to digitally filter the connected analog inputs and
calculate values. The calculated values are then available for all built-in protection and control
functions within the IED, which are connected to this preprocessing function block.
If frequency tracking and compensation is required (this feature is typically required only for
IEDs installed in the power plants) then the setting parameters
accordingly.
IED
2
(+)
(-)
4
SMAI2
BLOCK
AI3P
REVROT
AI1
^GRP2L1
AI2
^GRP2L2
AI3
^GRP2L3
AI4
^GRP2N
AIN
3
IEC11000029-4-en.vsdx
DFTReference shall be set
GUID-8EB19363-9178-4F04-A6AC-AF0C2F99C5AB v1
Section 4
Analog inputs
65

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 670 series

Table of Contents