Permissive Underreaching Scheme; Permissive Overreaching Scheme; Unblocking Scheme; Intertrip Scheme - ABB Relion REC670 Applications Manual

Bay control version 2.1 iec
Hide thumbs Also See for Relion REC670:
Table of Contents

Advertisement

1MRK 511 358-UEN A
14.1.3.3

Permissive underreaching scheme

Operation
Set
SchemeType
Set
tCoord
Set
tSendMin
Set
Unblock
Set
tSecurity
Set
14.1.3.4

Permissive overreaching scheme

Set
Operation
Scheme type
Set
Set
tCoord
tSendMin
Set
Set
Unblock
tSecurity
Set
14.1.3.5

Unblocking scheme

Unblock
Set
tSecurity
Set
14.1.3.6

Intertrip scheme

Set
Operation
SchemeType
Set
tCoord
Set
tSendMin
Set
Unblock
Set
tSecurity
Set
14.2
Current reversal and Weak-end infeed logic for
distance protection 3-phase ZCRWPSCH
14.2.1

Identification

Function description
Current reversal and weak-end
infeed logic for distance protection
3-phase
Application manual
On
=
Permissive UR
=
= 0 ms
= 0.1 s
Off
=
= 0.035 s
=
On
Permissive OR
=
= 0 ms
= 0.1 s (0 s in parallel line applications)
=
Off
= 0.035 s
Restart
=
(Loss of guard signal will give both trip and alarm
Choose
NoRestart if only trip is required)
= 0.035 s
=
On
Intertrip
=
50 ms (10 ms + maximal transmission time)
= 0.1 s (0 s in parallel line applications)
Off
=
= 0.015 s
IEC 61850
identification
ZCRWPSCH
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
85
Section 14
Scheme communication
M13869-25 v4
M13869-34 v4
M13869-43 v4
M13869-62 v4
IP15751-1 v4
M15073-1 v5
347