Section 16
Monitoring
after reaching the maximum count value. It is also possible to set the counter to rollover and
indicate the overflow as a pulse, which lasts up to the first count after rolling over to zero. In
this case, periodic pulses will be generated at multiple overflow of the function.
16.9.3

Setting guidelines

The parameters for Limit counter L4UFCNT are set via the local HMI or PCM600.
16.10

Running hour-meter TEILGAPC

16.10.1

Identification

Function Description
Running hour-meter
16.10.2

Application

The function is used for user-defined logics and it can also be used for different purposes
internally in the IED. An application example is to accumulate the total running/energized time
of the generator, transformer, reactor, capacitor bank or even line.
Settable time limits for warning and alarm are provided. The time limit for overflow indication
is fixed to 99999.9 hours. At overflow the accumulated time resets and the accumulation
starts from zero again.
16.10.3
Setting guidelines
The settings
resolution of the settings is 0.1 hours (6 minutes).
The limit for the overflow supervision is fixed at 99999.9 hours.
The setting
400
IEC 61850
identification
TEILGAPC
tAlarm and tWarning are user settable limits defined in hours. The achievable
tAlarm and tWarning are independent settings, that is, there is no check if
tAlarm > tWarning .
tAddToTime is a user settable time parameter in hours.
IEC 60617
ANSI/IEEE C37.2 device
identification
number
-
-
1MRK 511 358-UEN A
GUID-5AECCDBC-7385-4D9F-940C-9D4A0E59B106 v1
GUID-DA5DA8D7-4821-4BFB-86CC-28658E376270 v1
GUID-3F9EF4FA-74FA-4D1D-88A0-E948B722B64F v1
GUID-225D8341-2D31-49F1-9B49-571346C0FE26 v1
GUID-D3BED56A-BA80-486F-B2A8-E47F7AC63468 v1