Diagnostics
Error byte
hex
dec
16#08
8
The write command failed
16#09
9
Channel not configured
16#0A 10
Although the channel is configured
as a SERVER, an attempt was
made to initiate a read/write com-
mand
16#0B 11
Preceding read/write command not
yet completed
16#0C 12
Invalid command code
16#0D 13
All data transmissions were
aborted because a reconfiguration
was initiated by the user program.
16#80 128
There is no 24 V external supply
voltage
16#81 129
The channel being used is not
ready or is not operating properly
16#82 130
The channel being used is busy
16#83 131
A command with an unallowable
channel number was started
62
Description
Reaction / remedy
A new read/write command can
be initiated.
The parameters of the corre-
sponding write command
should be checked.
A new read/write command with
other parameters can be initi-
ated.
A new read/write command with
other parameters can be initi-
ated.
A new read/write command can
be initiated.
Evaluate the "DONE" return pa-
rameter of the preceding
read/write command
A new read/write command can
be initiated
Restart of the system
Wait until ready
Wait until ready
Evaluation of the return pa-
rameters of the ETHx_CTRL
subroutine
Wait until ready
A new read/write command can
be initiated
The user program should be
checked
09/02
Return
mechanism
Byte
Return
offset
value
in SM
(ETHx_)
area
25 - 32 _XFR
25 - 32 _XFR
25 - 32 _XFR
25 - 32 _XFR
25 - 32 _XFR
25 - 32
_XFR
33
_CFG
25 - 32
33
_XFR
_CFG
_XFR
_CFG
_XFR
CP 243-1
J31069-D0428-U001-A1-7618

Advertisement

Table of Contents
loading

Table of Contents