3.8.9. Temperature Hysteresis
Default Value: 1°C
Temperature hysteresis is the temperature difference between activation and
deactivation of an output stage (either the cooling or heating) during normal
operation.
3.8.10. Minimum Temperature Deadband (Read-Only)
Default Value: 2°C
Minimum temperature deadband between heat and cool setpoints. This deadband
feature prevents the thermostat to send heat and cool activation simultaneously.
When the temperature measurement of the room is within this zone (between heat
and cool setpoints), then no output stage is activated.
3.8.11. Temperature Minimum Setpoint
Default Value: 15°C
Minimum allowable temperature setpoint for a user.
NOTE: This parameter is set through network and is not accessible on the display
of the thermostat.
3.8.12. Temperature Maximum Setpoint
Default Value: 25°C
Maximum allowable temperature setpoint for a user.*
3.8.13. Temperature Stage Difference
Default Value: 1°C
Temperature difference between engagement of stage 1 and stage 2, for both heating
and cooling mode.
3.8.14. Compressor Min ON time
Default Value: 0 seconds
Once activated by the thermostat algorithm, the compressor output (Yx) will be kept
activated for a minimum period equivalent to Min ON time parameter.
3.8.15. Compressor Min OFF time
Default Value: 0 seconds
Once deactivated by the thermostat algorithm, the compressor output (Yx) will be
kept deactivated for a minimum period equivalent to Min OFF time parameter.